XLPE insulated control cable

XLPE insulated control cable is suitable for signal transmission, control and measurement system of electrical instruments and distribution devices with AC rated voltage of 450/750 V and below in metallurgical, electric power, petrochemical and other industrial and mining enterprises.

keyword:

XLPE insulated control cable

Category:

Product description

Product use

XLPE insulated control cable is suitable for signal transmission, control and measurement system of electrical instruments and distribution devices with AC rated voltage of 450/750 V and below in metallurgical, electric power, petrochemical and other industrial and mining enterprises.

XLPE insulated flame retardant control cable has the function of preventing fire from spreading in cable circuit, which can avoid the expansion of fire accidents and reduce losses.

The characteristic of XLPE insulated fire-resistant control cable is that it can ensure the normal operation of the cable line within a certain period of time under the condition of combustion, so as to facilitate the evacuation of people and rescue of important facilities.

XLPE insulated halogen-free and low-smoke control cable is suitable for signal transmission, control and measurement system of electrical instruments and distribution devices with AC rated voltage of 450/750 V and below in metallurgy, electric power, petrochemical and other industrial and mining enterprises, and has flame retardant and low-smoke performance.

Usage characteristics

Rated voltage

The rated voltage of cable U0/U is 450/750 V

Rated working temperature of conductor

The maximum rated working temperature of cable conductor is 90°C

The maximum temperature of cable conductor shall not exceed 250°C in case of short circuit (the longest duration shall not exceed 5 s)

Ambient temperature of laying

The ambient temperature of cable laying shall not be lower than 0°C, otherwise preheating in advance is needed

Installation bending radius

The installation bending radius of cable without armored layer shall not be less than 6 times the outer diameter of the cable

The installation bending radius of cable with armored layer or copper strip shielding structure shall not be less than 12 times the outer diameter of the cable

The installation bending radius of flexible cable with shielded layer structure shall not be less than 6 times the outer diameter of the cable

Product representation method

Code

Series code2)

Control cable………………………………………………………………………………K

Conductor code

Copper conductor (omitted)………………………………………………………………T

Insulation code

XLPE insulation……………………………………………YJ

Sheath code1)

PVC sheath………………………………………………………………V

Polyethylene sheath……………………………………………………………………………Y

Armored code

Double steel strip armored……………………………………………………………………………2

Thin round steel wire armored-……………………………………………………………………3

Code of outer sheath

PVC outer sheath…………………………………………………………2

Polyethylene outer sheath…………………………………………………………………3

Structural feature code

Soft conductor…………………………………………………………………………………R

Copper wire braided shielding………………………………………………………………………P

Copper strip wrapped shielding………………………………………………………………………P2

Note: 1) Including extruded inner lining and isolation sleeve, etc.

For flame retardant, fire-resistant, halogen-free low-smoke flame retardant cable series code, see Appendix C

Product model and composition

 

XLPE insulated control cable

 

Schematic Diagram of Product Structure

Schematic Diagram of Product Structure of XLPE Insulated Control Cable

 

123

Schematic Diagram of Product Structure of XLPE Insulated Flame Retardant and Refractory Control Cable

 

123

Product model and specification

Product model

Model

Product name

Scope of application and environment

Copper core

KYJV

Copper core XLPE insulated PVC sheathed control cable

Laying indoors, and in cable trench and pipeline fixing occasions

KYJVP

Copper core XLPE insulated PVC sheathed copper wire braided shielded control cable

Laying indoors, in cable trench, pipeline and other fixed occasions requiring shielding

KYJVP2

Copper core XLPE insulated PVC sheathed copper strip shielded control cable

KYJV22

Copper core XLPE insulated PVC sheathed steel strip armored control cable

Laying indoors, in cable trench, pipeline, directly buried and other fixed occasions that can bear large mechanical external force and so on

KYJVP22

Copper core XLPE insulated PVC sheathed copper wire braided shielded steel strip armored control cable

Laying indoors, in cable trench, pipeline, directly buried and other fixed occasions that can bear large mechanical external force and require shielding

KYJVP2-22

Copper core XLPE insulated PVC sheathed copper strip shielded steel strip armored control cable

KYJV32

Copper core XLPE insulated PVC sheathed fine steel wire armored control cable

Laying indoors, in tunnel, cable trench, shaft or buried and other occasions that can bear mechanical external force and certain pulling force

KYJVR

Copper core XLPE insulated PVC sheathed flexible control cable

Laying in indoor movement occasions that require softness and shielding

KYJVRP

Copper core XLPE insulated PVC sheathed braided shielded control flexible cable

Product specification

Rated voltage, nominal section of conductor section and number of cores

Model

Rated voltage/V

Nominal cross-sectional area of conductor/m㎡

0.5

0.75

1

1.5

2.5

4

6

Number of cores

KYJV

450/750V

-

2~61

2~14

KYJVP

-

2~61

2~14

KYJVP2

-

4~61

4~14

KYJV22

-

7~61

4~61

4~14

KYJV32

-

19~61

7~61

2~14

KYJVR

4~61

-

KYJVRP

4~61

4~48

-

KYJVP22

-

7~61

4~61

4~14

KYJVP2-22

-

7~61

4~61

4~14

Main technical performance of products

There are three types of conductive wire cores: The first (A) and the second (B) are suitable for fixed laying (the first is solid conductor and the second is twisted conductor); and the third (R) is stranded soft conductor, which is suitable for flexible cables with mobile requirements

Conductor structure and DC resistance shall comply with Appendix A

Insulated wire core can be identified by color mark or digital mark

The insulated wire core shall be subjected to power frequency spark test, and the effective value of the test voltage is 6 kV

The cable can withstand the withstand voltage test of 50 HZ, 3000 V and 5 mins of AC

The bundle flame retardant, fire-resistant and halogen-free low-smoke flame retardant performance shall comply with Appendix B

Insulation resistance

Nominal section(m㎡)

Insulation resistance MΩ·km≥

20℃

90℃

0.5

1300

1.3

0.75

1200

1.2

1.0

1100

1.1

1.5

1100

1.1

2.5

1000

1.0

4

850

0.85

6

700

0.7

10

650

0.65