Low voltage power cable(0.6-1kV)
keyword:
Category:
Product description
0.6/1 kV PVC insulated and vinyl chloride sheathed power cable
Product use
This product is suitable for power supply and distribution in lines with AC 50 Hz rated voltage of 0.6/1 kV.
Usage characteristics
-
The maximum rated temperature of cable conductor is 70°C.
-
The maximum temperature of cable conductor shall not exceed 160°C during short circuit (the longest duration shall not exceed 5 s).
-
When laying cables, the ambient temperature shall not be lower than 0°C. The minimum bending radius is: for single-core unarmored cables, 20 times the outer diameter of cable; for single-core armored cables, 15 times the outer diameter of cable; for multi-core non-armored cables, 15 times the outer diameter of cable, and for multi-core armored cables, 12 times the outer diameter of cable.
Model, name and scope of use


* L is aluminum core
Structure size of cable
VV,VLV,ZRVV,ZRVLV
0.6/kV PVC insulated PVC sheathed flame retardant or non-flame retardant power cable





Vv22,VLV22,ZRVV22,ZRVLV22
0.6/1 kV PVC insulated steel strip armored PVC sheathed flame retardant or non-flame retardant power cable





Current carrying capacity of cable
VV,ZRVV
Permissible current carrying capacity of 0.6/1 kV copper conductor PVC insulated PVC sheathed flame retardant and non-flame retardant power cables laid in air under long-term continuous load.


VLV,ZRVLV
Permissible current carrying capacity of 0.6/1 kV copper conductor PVC insulated PVC sheathed flame retardant and non-flame retardant power cables laid in air under long-term continuous load.

VV22,ZRVV22
Permissible current carrying capacity of 0.6/1 kV copper conductor PVC insulated PVC sheathed flame retardant and non-flame retardant power cables laid in air under long-term continuous load.

VLV22,ZRVL22
Permissible current carrying capacity of 0.6/1 kV copper conductor PVC insulated PVC sheathed flame retardant and non-flame retardant power cables laid in air under long-term continuous load.

Cable operation and laying conditions
Cable laying
-
When laying, the cable temperature shall not be lower than 0°C, and when the ambient temperature is lower than 0°C, the cable shall be preheated.
-
The minimum bending radius for laying is: for single-core unarmored cables, 20 times the outer diameter of cable; for single-core armored cables, 15 times the outer diameter of cable; for multi-core non-armored cables, 15 times the outer diameter of cable, and for multi-core armored cables, 12 times the outer diameter of cable.
-
After the cable is laid, it shall undergo DC withstand voltage test for 15 minutes and the test voltage is 3.5 kV.
Laying in the air
-
When single-core cable is laid in parallel, the center distance is: for 185 mm and below, 2 times the cable diameter, and for 240 mm and above, 90 mm.
-
Ambient temperature: 30℃。
-
Maximum allowable temperature of conductive core: 70℃。
-
Correction coefficient of carrying capacity at different ambient temperatures

Directly buried laying
-
When single-core cable is laid without contact, the center distance is 2 times the cable diameter.
-
Ambient temperature: 25℃
-
Maximum allowable temperature of conductive core: 70℃
-
Thermal resistance coefficient of soil: 1.0℃.m/w
-
Straight and deep: 0.7mDepth: 0.7m.
-
Download flow correction coefficient at different ambient temperatures:

0.6/1 kV PVC insulated and sheathed refractory power cable

Product use
This product is used in high-rise buildings, subways, power stations and other important occasions with fire safety and fire lifesaving capabilities.
Usage characteristics
0.6/1 kV PVC insulated and sheathed refractory power cable is designed and produced according to GB/T12706-2008 (equivalent to IEC60502 standard), and its physical and electrical properties are the same as those of ordinary plastic cable. Its fire resistance meets GB/T19666-2005. That is to say, the cable can maintain normal operation for 90min under rated voltage of 0.6/1 kV and flame combustion at 750-800°C.
Model and name

Note: Single core is used in AC system, and non-magnetic metal strip is used
Related products
Product inquiry
Henan Yuelong Jinke Cable Co., Ltd.
Add : Ying Jun Lu, Ying Fangkou Industrial Park, Gu County Town, Yanshi City, Luoyang City, Henan Province
Tel : +86 13663794466
E-mail : yljkdl@126.com
scan
Mobile terminal
Copyright © 2023 Henan Yuelong Jinke Cable Co., Ltd. This site has supported ipv6